Structural safety of wood decks and deck guards

Photo © BigStockPhoto/LeeBarnwell
Photo © BigStockPhoto/LeeBarnwell

by Joseph R. Loferski, PhD, and Frank E. Woeste, PE, PhD
Most residential deck-related accidents are caused by failure of the deck-to-house connection or of the guardrail system, which can cause a person to fall from the deck, resulting in serious injuries or death.

A sample of accident reports is given in Figure 1. Additionally, the authors have partial data dating back to 2001, showing the problem is widespread; accidents occur in nearly every region of the United States. The news reports often state the cause of a catastrophic deck failure was ‘over-loading.’ Based on media reports and the authors’ own investigations, however, many of the subject decks should have safely carried their load without collapsing.

Several media reports showing a sampling of deck collapses in the United States.
Several media reports showing a sampling of deck collapses in the United States.

Why do some decks and guards fail and cause injuries? Several reasons for deck failures have been observed, including inadequate fasteners and connections, corrosion, improper materials, construction defects, and wood decay.

Decks are often designed as a collection of individual parts, rather than as a unified system of interrelated components. For example, the failure of the deck ledger connection to the house may be due to a combination of factors, including no or improper flashing leading to decay in the house band joist, and improper or inadequate fasteners. Guard failure is most commonly caused by failure of the connection of the guard post to the deck, the connection of the rails to the post, or connection of the pickets to the rails. Further, because decks are exterior structures permanently exposed to weather, long-term decay or fastener/connector corrosion is more likely, and can contribute to a failure.

This article specifically addresses residential decks, but multi-family and light commercial decks, balconies, and guards—with more demanding code requirements—can have similar failure modes, making the general concepts quite pertinent. The architect and specifier should exercise great care and diligence when specifying deck or balcony-type structures (and related guards) as they are likely to require expertise in waterproofing specifications and details. (See “Multi-family Balconies.”)

Problem overview
Deck collapses and guard failures generally can be traced to designers and contractors who focus on parts and components rather than taking a holistic approach. For example, a through-bolted connection between the guard post and the deck band joist rarely fails. However, the connection of the band joist to the deck joist often uses nails or screws inserted in the end-grain of the joists. Since the guard post is at least 914 mm (36 in.) above the deck surface, it acts as a lever, causing the band joist to ‘peel’ away from the joists.

Photo of a typical deck attached to house; the circle shows the ledger connection. [CREDIT] Photos courtesy Joseph Loferski
Photo of a typical deck attached to house; the circle shows the ledger connection. Photos courtesy Joseph Loferski

The 2012 International Residential Building Code for One- and Two-family Dwellings (IRC) does not include a prescriptive method or detail for connecting a guard post to a deck substructure. Therefore, many contractors are faced to determine what is needed for a safe guard post connection without any code guidance, except for the vague 890-N (200-lb) concentrated load requirement in IRC.

Specific language and prescriptive details in a future IRC edition on how to make a connection of the guard post to the deck that will safely resist this 890-N load is desperately needed by all parties involved—specifiers, architects, engineers, contractors, home inspectors, and the building code enforcement community.

IRC does contain prescriptive guidelines for bolt and lag screw attachment of deck ledgers to a solid-sawn house-band, based on work by the authors at Virginia Tech University in collaboration with researchers at Washington State University.1

Deck ledger testing at Virginia Tech showing load application and deflection measurement made with a LVDT.
Deck ledger testing at Virginia Tech showing load application and deflection measurement made with a LVDT.

Design considerations for ledgers
Most often, decks are attached directly to the house using bolts or lag screws that connect the ledger to the house-band. On the other side, the deck is supported by a beam resting on columns bearing on concrete footings as shown in Figure 2.

Deck ledger connection tests were conducted to develop bolt and lag screw spacing requirements for various commonly used deck designs.2 Figure 3 shows a deck ledger connection being tested for gravity load capacity. The test used a 2×10 (nominal) to simulate the house band and a 2×8 (nominal) pressure-preservative-treated (PPT) member to simulate the deck ledger. Two simulated deck joists were attached to the ledger. The load was applied to the joists until failure. A transducer measured the ledger’s deflection relative to the band joist.

The results were used to compute fastener spacing requirements based on tested capacity of the connection. IRC Table R507.2 (Figure 4) gives the ledger connection requirements, and IRC Section R507.2.1 provides the required placement of bolts or lag screws in the deck ledger connection. All parties involved must closely review the design assumptions and limitations in the caption (e.g. live and dead loads) and footnotes to Table R507.2.1.

Proper screw and bolt installation requirements—American Wood Council’s (AWC’s) National Design Specification (NDS) for Wood Construction with 2012 Supplement—must be followed for the fastener spacing requirements listed in the table.

Data courtesy International Code Council
Data courtesy International Code Council

Another consideration is the type of lumber and posts used to build the deck. Using alkaline copper quaternary (ACQ) and copper azole (CAB) wood preservatives is now common for deck construction. These preservatives are generally known to be more corrosive to steel fasteners than chromated copper arsenate (CCA) preservatives. Therefore, corrosion-resistant fasteners such as hot-dipped galvanized steel or stainless steel must be used for reliable performance.

Some decay fungi are ‘copper limited,’ meaning they can colonize wood products treated with copper-based preservatives such as ACQ and CAB.3 Research has shown even wood treated to ‘ground contact’ treatment retention levels may experience fungal decay.4 So, embedding support posts into the ground may not be the best option. To improve deck post longevity, posts should be placed on concrete piers above ground-line and connected with a corrosion-resistant post-connector to the concrete piers. While not necessarily a code requirement, 6×6 (minimum) posts are recommended for aesthetic reasons and are much less likely to undergo severe warp (i.e. bow and twist).

Typical deck guard system showing posts, rails, and pickets. [CREDIT] Photo courtesy Joseph Loferski
Typical deck guard system showing posts, rails, and pickets. Photo courtesy Joseph Loferski
Properly installed flashing between the deck and house to prevent water infiltration into the wall sheathing and house band is extremely important. The typical house band joist (or engineered rim board) is not made from PPT lumber. Therefore, water intrusion into the wall section can lead to wood decay around the bolt or lag screw and thus failure of the connection. Proper flashing and caulking is needed to keep the house band dry, preventing decay. Due to the difficulty of achieving a reliable waterproofing system, a PPT house band—with compatible corrosion-resistant fasteners—at the deck attachment location is recommended.

Other system considerations include lateral bracing for both house-attached and freestanding decks. In Section R507.2.3 and Figure R507.2.3, IRC includes a prescriptive detail that can be used to meet the code requirements for lateral deck stability. The detail shows a connection from the deck joists to the house joists, and it requires a design load capacity of 6.67 kN (1500 lb). At least two such connectors are required for the deck’s lateral bracing.