
(2) Access-control systems utilizing electric strikes typically allow free egress via the lever handle or panic hardware, and are not subject to any special code requirements for egress.
(3) Delayed egress hardware requires signage on the door stating, “Push until alarm sounds. Door can be opened in 15 seconds.” The use of delayed egress locks is limited by occupancy type.
Other hardware
In addition to electromagnetic locks, there are several other types of electrified hardware used with access control systems, with varying code requirements.
Controlled access/free egress
Controlled access/free egress is probably the most common application for doors with access control. The reader device limits access, but the door hardware allows free egress at all times, independent of the access control system. The door hardware may be:
- an electrified lockset;
- mechanical lockset with electric strike;
- electrified panic hardware; or
- other combination allowing free egress.
This hardware is subject to the same requirements as standard mechanical hardware. Per the 2009 IBC, it must be “readily openable from the egress side without the use of a key or special knowledge or effort” (1008.18). If the door is required to be accessible, the hardware “shall not require tight grasping, tight pinching, or twisting of the wrist to operate” (1008.1.9.1), and it “must be installed [864 mm] 34 in. minimum and [1219 mm] 48 in. maximum above the finished floor” (1008.1.9.2). NFPA 101-2009’s Section 7.2.1.5.1 contains similar requirements.
Delayed egress locks
When there is a desire to control egress as well as access, delayed egress hardware may be used depending on the occupancy type and other code conditions, such as a requirement for the building to be protected throughout with an automatic sprinkler system or an approved automatic smoke/heat detection system. The delayed egress lock will prevent egress for 15 seconds (or 30 seconds when approved by the authority having jurisdiction [AHJ]) when initiated by a 67-N (15-lb) force, but will release immediately upon fire alarm or power failure. Other conditions for using delayed egress locks include:
- signage;
- an audible local alarm;
- capability of remote release;
- limitations on the number of delays in an egress route; and
- emergency lighting.
There are variations between the 2009 IBC (1008.1.9.7) and NFPA 101 (7.2.1.6.1) in regard to delayed egress locks—for example, the amount of time the activating force may be applied is one second in the former and three in the latter. Additionally, IBC prohibits use of delayed egress locks on Assembly, Educational, and High-hazard occupancies, while NFPA 101 has different stipulations for occupancy classifications where delayed egress locks are allowed.
Stairwell doors providing re-entry
In most cases, IBC requires all stair doors that are locked (with the exception of the stair discharge door), to allow re-entry during a fire alarm. In other words, a door normally kept locked on the stair side for security purposes would be unlocked during a fire. This way, a building occupant can leave the stair if it becomes compromised, and seek another exit. These unlocked stair doors also allow firefighters access to each floor. The 2003 edition of IBC allows mechanical locks on the stair side of doors serving four stories or less, but this exception has been removed from the later editions.
To meet the stairwell re-entry requirements, fail-safe locks are installed, which allow free egress to the stair at all times, and can be remotely controlled from the fire command center or the fire alarm system to permit access from the stair side.
These fail-safe locks remain latched when they are unlocked, as required for fire doors. The 2009 NFPA 101 (7.2.1.5.7) has slightly different requirements for stairwell re-entry from the 2009 IBC (1008.1.9.10 and 403.5.3), including an exception that allows stairs serving four stories or less to be mechanically locked on the stair side, and a set of conditions called “Selected Re-entry.” These would only be applied to buildings where NFPA 101 is the prevailing code, as the IBC does not include such provisions.

Elevator lobby doors
When an elevator lobby does not have direct access to a stairwell, egress through the tenant space to an exit may be required. The 2009 NFPA 101 addresses this in a new section, “Elevator Lobby Exit Access Door Assemblies Locking” (7.2.1.6.3). IBC does not have a separate section pertaining to the locks on elevator lobbies, but states, “elevator lobbies shall have at least one means of egress complying with Chapter 10 and other provisions within this code” (708.14.1). One way of doing this involves employing delayed egress locks, but this application reduces security and requires signage that can be confusing when mounted on a door typically used for entrance to the tenant space. Some state and local codes have adopted requirements for elevator lobby doors which are more similar to the NFPA 101 requirements.
Healthcare special egress locks
The 2009 editions of IBC (1008.1.9.6) and NFPA 101 (18.2.2.2.5) contain new requirements pertaining to the locking of egress doors in certain units within healthcare facilities, where the clinical needs of those receiving care require such locking. The new sections describe locks that unlock upon actuation of the fire alarm/sprinkler system
or power failure, that can also be unlocked remotely or by clinical staff at all times. Before installing these systems, the requirements of the Joint Commission and the Centers for Medicare and Medicaid Services (CMS) must be considered. [These organizations are currently using the 2000 edition of NFPA 101 for their inspections (though they may be moving to the 2012 version soon), which means the new sections are not there—facilities would have to ask the organizations for permission to do something acceptable by the current code, but not by the code the organizations are using.]
Conclusion
As this article illustrates, applications actually classified as “access-controlled egress doors” are limited. When considering which code requirements to follow, a specifier should first identify which category the hardware falls into, and then refer to the applicable section.
This summary is not intended to provide complete information about each type of access control doors referenced (for more information, refer to related articles on iDigHardware.com). It is also important to keep in mind state or local requirements could differ from those of IBC or NFPA 101, so design professionals must be aware of the codes in their project’s jurisdiction. Published codes should be referred to for the detailed code requirements, and AHJs should be consulted for more information about the local codes.
Lori Greene, CSI, AHC/CDC, CCPR, FDAI, is the codes and resources manager for Ingersoll Rand Security Technologies. She has been in the industry for more than 25 years, and used to be a hardware consultant writing specifications. Greene is a member of the Construction Specifications Institute (CSI), the Door and Hardware Institute (DHI), the International Code Council (ICC), the National Fire Protection Association (NFPA), and the Builders Hardware Manufacturers Association (BHMA) Codes and Government Affairs Committee. She has a monthly column on code issues in Doors & Hardware, and blogs at www.iDigHardware.com. Greene can be contacted via e-mail at lori_greene@irco.com.
We have a few On-Call Dr Sleep Rooms in our Hospital. They want a push-button keypad for entry with a deadbolt and a swing bar on the inside of the door for privacy. The entire building is fully sprinklered. Will this meet NFPA code?
I would call it a code violation. Not having free egress out of the room would cause issues. Entering into the room with a keypad if fine, there is an electronic lock out there that has a lock on the inside for like bathrooms or meeting rooms, once the interior lock is pushed you can’t get into the room until someone comes out or releases the lock.
Thank you for sharing this informative article. I am looking forward to your next post!
When it says this request the exit button must be within 5 feet of the door, is this 5 feet from the door handle or 5 feet from any part of the door?
It’s like a fire alarm, the pull station has to be “within” 5 foot of the door @ ADA height. Right side / left side doesn’t matter, but you can’t go out of you way to get to it, it has to be free egress.
Is it against building code to disconnect the alarms system on an emergency exit door in a nursing home where someone can also leave door ajar as anyone can enter building without notice
Hello, I have a manager putting in a barcode access to my home, apartment? I have considerable concerns. Who is putting this device in. Do they have to be legally bonded to ; as being some kind of legal inspector? I live in CA. And I have no information yet who is doing this. But I’m concerned because of a different type of cyber attack as in, entering my apartment. And I know my brother had to undergo, legalitys to put in security for the police. Cyber stuff. Please, help me her.