Managing the risks of efflorescence

by sadia_badhon | January 2, 2019 4:55 pm

by Michael Micalizzi, CTC

All photos courtesy Custom Building Products[1]
All photos courtesy Custom Building Products

The costs of cleaning efflorescence from grout joints and tile surfaces can range from a lost day on a callback to a financial fortune, depending on the size and type of project on which it occurs. For example, to acid-wash tile on one large project, remediation costs exceeded $100,000 for the labor and the scaffolding. Additionally, the owners were highly concerned by the acid-wash residue potential over the window trims and plantings, expressing fears regarding risk to occupants entering and leaving the building. Often, these issues lead to hiring consultants and attorneys.

Standing water results in efflorescence.[2]
Standing water results in efflorescence.

Efflorescence occurs when mineral salt deposits that have leached or migrated from cement and masonry materials are carried to the surface in moisture vapor. These minerals occur naturally in Portland cement and, when dried, appear as a white film, powder, or crystal. Many kinds of mineral salts have been detected in samples of efflorescence, including sodium sulfate, potassium sulfate, sodium carbonate, calcium sulfate, sodium bicarbonate, and calcium carbonate.

The tile industry has experienced efflorescence for a very long time. Unfortunately, building owners and general contractors (GCs) often believe it is solely the tile contractor or installation material supplier’s responsibility to both prevent it from happening and remove it when it occurs. Although poor installation methods can cause it and certain products are more susceptible to it, in many cases, building design and product selection causes or contributes to the problem in both interior and exterior applications.

New concrete and mortar beds will provide a source for efflorescence in a wide variety of projects. For example, when porcelain tiles are installed in exterior applications, the mortars used are polymer-modified, so when the standard-setting, Portland cement-based mortars are used instead of rapid-curing, calcium aluminate-based types, they retain moisture for an extended time, adding to the possibility of salt migration.

Efflorescence from minerals in natural stone.[3]
Efflorescence from minerals in natural stone.

 

To prevent this issue, it is important to address the main causes resulting in or contributing to efflorescence, namely:

Design/construction professionals will likely be familiar with many of these issues, but unfamiliar problems may catch a team by surprise.

Tile installation practices

A contractor’s proper, moderate, and controlled use of water during an installation is critical to lessen the risk of efflorescence. Over-watering grout, using too much water to finish grout, and leaving excess water on the tile or grout surface can result in a light residue or substantial blooms of efflorescence.

Figure 1 Placement of a drainage mat in a tile/stone assembly aids in water evacuation.[4]
Figure 1: Placement of a drainage mat in a tile/stone assembly aids in water evacuation.

Efflorescence forms due to soluble salts within a concrete substrate, a mortar bed, installation materials, and/or grouts. When water acts as a carrier of the salts through grout, they dry and crystallize on the tile surface as they are exposed to air. Even some tiles and natural stone varieties (typically cement and sedimentary stones such as limestone) can also effloresce when exposed to water. Excessive use of water can easily start the reaction, especially when site conditions are cold or humid or when heat draws moisture from a damp substrate or tile assembly.

Efflorescence caused by poor mortar coverage.[5]
Efflorescence caused by poor mortar coverage.

Manufacturers recommend an acceptable water range for mixing and recommend waiting until grout gels or firms before finishing. Otherwise, the unreacted grout will be damaged. Washing should always be done with a damp sponge, not a wet or soaked one that may flood the joint and leave puddles.

Mortar coverage of less than a rate of 95 percent under a tile or stone in wet areas, in either a vertical or horizontal application, allows water to flow or set on cement adhesives and substrates. As the water evaporates, it allows formation of efflorescence under the tiles (also known as subflorescence or cryptoflorescence), which later finds its way through grout and sealant joints. This cycling effect of efflorescence formation can also contribute to bond failure, as these minerals expand below and around the tile, creating compression at the bond interface and between tiles.

Efflorescence from concrete substrate.[6]
Efflorescence from concrete substrate.

Additional installation errors in flatness and pitch of components in the tile assembly can easily lead to efflorescence. The requirement for proper drainage on horizontal surfaces in wet areas is 6 mm (¼ in.) per linear foot. This requires preparation work to the substrate (pre-slope), the mortar bed, and the waterproofing or crack isolation membrane. The tile or stone must also be in plane with the pitch. Slight birdbaths in the substrate, mortar bed, or tile lippage will slow or prevent water from draining, resulting in concentrations of salts and efflorescence. Often overlooked is the need for grout to be consistent in depth and smoothness and as close to the tile surface as possible.

Other related components of a tile assembly, such as a floor drain, must have effective weep holes and proper tile edge heights around them for good water drainage. When sealant or grout is very low around the drain flange, water evacuation is slower than the time it takes to dry, and efflorescence forms in these areas. Sealant in other movement joints can also be problematic if not properly detailed with sufficient product forced into the joint to adhere to the tile edges or placed over backer rod per Adhesive and Sealant Council (ASC) recommendations. Since these joints begin either below the concrete or at the substrate level, they are a faster pathway to the surface for efflorescence.

Installation materials

Extreme efflorescence due to improper installation.[7]
Extreme efflorescence due to improper installation.

Portland cement products naturally contain lime, which is a source of the salts that migrate to the tile surface. Practically every installation material manufacturer disclaims liability for efflorescence formation with Portland cement products for this reason. Concrete, plasters, mortar beds, dry-set mortars (thin-sets), grouts, and some tiles are manufactured with Portland cements. So, efflorescence is difficult to avoid, but it can be controlled. There are alternative products available that greatly lower the possibility and eliminate some of the sources of these salts. When such products are used as a system, the risk of efflorescence is very low.

It is crucial to take steps to prevent efflorescence.[8]
It is crucial to take steps to prevent efflorescence.

The first step is to include a flat membrane (such as a liquid- or sheet-applied type) able to restrict water from entering the substrate. Concrete and other cement substrates are the most likely culprits to provide a source for efflorescence in an assembly, so this can significantly reduce the risk of this problem. Due to their geometric cavities, uncoupling mats may also trap or slow water from draining and result in efflorescence. Adding a drainage mat under a mortar bed in exterior applications instead of using a cleavage membrane will be a great help to move water to a membrane and out of the assembly (Figure 1, page 30).

Figure 2 The effects of reducing slope in a tile assembly with allowable installation variables.[9]
Figure 2: The effects of reducing slope in a tile assembly with allowable installation variables.

Second, mortars and grouts made with calcium aluminate (CA) cements or blends of primarily CA are much less likely to contribute to efflorescence, as these cements contain little or no lime. These product formulations are exothermic and cure quickly, using up water at a faster rate. Many manufacturers advertise they will not contribute to efflorescence or effloresce at all. This is especially important in cold and damp conditions. Premixed or single-component grouts 
and epoxy grouts are another option, as they are noncementitious, typically free of efflorescence, and warranted to be so.

To help prevent minerals from migrating out from cement-based tiles or natural stone, penetrating sealers might be a solution. To adequately accomplish this, a ‘six-sided’ sealing process is employed, in which the stone is immersed in certain sealers that, after removal, are allowed to dry till the next day. Some penetrating sealers will allow adhesion with cement mortar.

Project design options and flaws

Numerous design choices can lead to the formation of efflorescence. One of the most common is reducing the substrate and assembly pitch from 6 mm (¼ in.) per foot to 3 mm (1/8 in.) per foot. This is most often proposed with accessible showers and exterior decks/balconies where the elevations have not been properly accounted for or the design team feels the pitch is too severe. As shown in Figure 2, this reduction severely impacts the margin of error for even the best tile contractor due to acceptable variances in the installation and the tile itself, and actual pitch could be reduced to 0.7 mm (1/32 in.). What makes things worse is the tiles and natural stone recommended for these areas are purposely profiled, rough, or clefted to provide adequate slip resistance. That also means they will slightly slow down water flow or prevent water from draining, resulting in ponding and formation of salt deposits.

Efflorescence caused by incorrect slope.[10]
Efflorescence caused by incorrect slope.

Construction schedules and budgets all too often push the limits on risks with regard to the surface preparation, curing timeframes, or added products that would manage efflorescence and potential failures. For example, rapid-setting mortars and cement grouts or noncementitious grouts and waterproofing membranes used in a system may be more expensive, but can limit the risk to a minimum. Waterproofing or moisture mitigation is often ‘value engineered’ out of the specification, proper sloping is eliminated, or tile is direct bonded over fresh concrete. Most tile contractors have been told at one time or another, “I need it installed now! Just put it in or I will have to get someone else.” In such situations, the possibility of efflorescence is not considered.

Proper flashing using a drip edge.[11]
Proper flashing using a drip edge.

Exterior roofing and façades require a design able to effectively evacuate or shed water. Another common flaw is poor detailing of drip edges or the elimination of them altogether at a rooftop or around windows. When water is allowed to seep behind a tile, it will eventually find a way out, bringing with it minerals and salts. An extended drip edge and gutter will help keep water off the sides of the building (Figure 3, page 34). Also, at times, a stone façade is chosen that does not allow for grout in the joints. It can be expected efflorescence can occur in this design, as water is freely allowed into the bonding mortar and substrate, allowing easier salt migration.

Proper design of movement joints in every assembly relieves the stresses of normal building movement from any deflection, loads, and thermal changes. However, when expansion joints are inadequate, tile expansion and the resulting compression cracks grout or loosens tile, creating fissures for water and moisture to pass through and draw out minerals from below. It should also be noted dark-colored tiles absorb and retain much more heat, a factor leading to increased expansion and fractured grout without adequate movement space.

Rising moisture brings minerals to the tile and grout surface.[12]
Rising moisture brings minerals to the tile and grout surface.

Irrigation systems have also been known to create cycles where the assembly is saturated and dries repeatedly. Typically, sprinklers supply water in the early morning, and as the sun rises, heat draws out moisture along with minerals and salts. Improper grading also mismanages water flow. Worse, some water used for irrigation could have greater potential to cause efflorescence if it is reclaimed and rich in minerals.

Since anyone’s actions on a project could cause the appearance of efflorescence, it should be an important consideration for every installation. Each person involved should reflect on what steps can be taken to help manage risks. Important strategies include performing a mockup to evaluate results, along with incorporating industry best practices such as creating adequate substrate and waterproofing pitch, edge detailing, and acceptable adhesive mortar coverage. Not to be overlooked is heating or tenting the installation in extreme temperatures and providing protection from weather during curing. The material supplier will also have suggestions and warranty requirements for the product and assembly installation conditions, along with their protection.

When working on a fast-track project or noticing anything that could cause a problem, one should notify the whole team of the possible risks and determine who is responsible for the remediation.

In the words of former U.S. general Colin Powell, “There are no secrets to success. It is the result of preparation, hard work, and learning from failure.”

Michael Micalizzi, CTC, is the senior director of technical services for Custom Building Products, and possesses more than 33 years of industry experience. In his current role, Micalizzi assists industry professionals with recommendations on commercial projects for various installation challenges. Prior to becoming involved in product technology, Micalizzi owned a tile and stone installation company in New Haven, Connecticut. He currently serves on technical committees for the Tile Council of North America (TCNA), American National Standards Institute (ANSI), ASTM International Materials & Methods Standards Association (MMSA), National Tile Contractors Association (NTCA), and Natural Stone Institute (NSI). Micalizzi can be reached via e-mail at mmicalizzi@cbpmail.net[13].

Endnotes:
  1. [Image]: https://www.constructionspecifier.com/wp-content/uploads/2019/01/Efflorescence.jpg
  2. [Image]: https://www.constructionspecifier.com/wp-content/uploads/2019/01/stone-shower-floor.jpg
  3. [Image]: https://www.constructionspecifier.com/wp-content/uploads/2019/01/Efflorescence-on-Serpentine-004.jpg
  4. [Image]: https://www.constructionspecifier.com/wp-content/uploads/2019/01/Deck-Detail.jpg
  5. [Image]: https://www.constructionspecifier.com/wp-content/uploads/2019/01/DSC00160.jpg
  6. [Image]: https://www.constructionspecifier.com/wp-content/uploads/2019/01/Efflorescence-Concrete-2.jpg
  7. [Image]: https://www.constructionspecifier.com/wp-content/uploads/2019/01/pass-the-salt-please.jpg
  8. [Image]: https://www.constructionspecifier.com/wp-content/uploads/2019/01/Efflorescence-Porcelain-Tile-Wall.jpg
  9. [Image]: https://www.constructionspecifier.com/wp-content/uploads/2019/01/Deck-Slope.jpg
  10. [Image]: https://www.constructionspecifier.com/wp-content/uploads/2019/01/DSC00131.jpg
  11. [Image]: https://www.constructionspecifier.com/wp-content/uploads/2019/01/Deck-Flashing-1.jpg
  12. [Image]: https://www.constructionspecifier.com/wp-content/uploads/2019/01/Efflorescence-Grout-1.jpg
  13. mmicalizzi@cbpmail.net: mailto:mmicalizzi@cbpmail.net

Source URL: https://www.constructionspecifier.com/managing-the-risks-of-efflorescence/